Anchor Data Centre Specifications
Facility Summary
| AC power | To support all racks 15 Amp single phase to 32 Amp
three phase |
| DC Power | Available |
| UPS | 120 kVA dual feed with infrastructure in place to total 240 kVA with
100% diversity, 1 hour minimum back up |
| A/C | Under floor distribution with top return; Multiple water cooled
condensers to support full accommodation of the area with 20% extra capacity;
Cooling towers servicing Sydney Co-Location 1 & 2 |
| Preaction fire protection | Dual, above and under raised floor
|
| Vesda smoke alarm | Dual, above and under raised floor |
| Gaseous fire protection (FM200) | Dual, above and under raised
floor |
| Generator | 870 kVA with fuel capacity to last 3 days 24 hour run with no
refill |
| Raised floor | 500 mm high with under floor cable tray system, air
conditioning, dual fire protection and smoke detection system |
| Cable tray system | Under floor system |
| Fibre delivery system | Above ground - ducted. Top entry
required to racks |
| Lifting platform | 1 T to raise equipment to raised floor
level |
| Racks | 19" by 47 RU, supplied, installed and pre-wired by Anchor, fully
enclosed with glass anti-static door, lockable, bottom entry for air, power
and data cabling, fibre top entry, top exhaust air |
| Security | Access card with escort.
Card Access required for both the floor & room.
CCTV on doors & cabinet rows |
Service Components
Power
All sites are designed to provide sufficient power supplies to service all
equipment within each facility. All power is backed up by specifically
designed back up facility such as generator and UPS.
Direct Current (-48V DC)
All facilities are equipped with state of art Direct Current (DC) equipment.
The equipment generally consists of rectifier(s), batteries and distribution
equipment/boxes.
4-hour batteries are installed at all sites. All batteries are charged from
mains (AC) supply. Custom designed, installed and methodically maintained
emergency diesel generator automatically backs this up.
Loss of power is immediately visible at NOC from all sites. NOC manned
24x7x365 to respond immediately to any loss of power.
Alternate Current (240V AC)
AC power will be supplied as an option to the Co-Location customer. AC will
be supplied between 10 to 32 Amp single phase. If the customer will require
3-phase supply this can be accommodated up to 32 Amps 3 phase.
UPS
All AC power is protected by UPS backup.
Generator Back-Up
AC power supply is backed up at all sites by generator and ancillary
equipment. All generator systems are supplied with fuel tanks with fuel
capacity of minimum 3 days, 24 hours per day at maximum loads.
Generators are appropriately maintained and test run on monthly basis. The
service and test runs do not require shut-down. Operations and Customer Care
will coordinate with customers to ensure they are aware of impending tests.
These shutdowns do NOT cause any loss of power to customer equipment.
Floor coverings
All floors are covered by antistatic vinyl.
Grounding
All sites have dual grounding protection:
Building earth - all racks, cable trays and non-communication equipment is
bonded to it
Technical (Communications) earth – all communication equipment is bonded to it
via communications earth bars located within the racks.
Fire Protection
Fire protection is provided at Anchor Co-Location sites in the following form:
VESDA smoke detection and alarm system
Pre-action fire protection
FM 200 gaseous system
Connection to house fire control system
Alarms are visible by NOC from all sites
Air Conditioning
All sites have minimum 20% redundant capacity of cooling.
Air conditioning is specifically designed to site-specific conditions to
deliver constant environmental climate of 22°C and humidity level of 49%.
Air conditioning units are state of art design. Units are either water or
air-cooled. Where water coolers are employed minimum of 20% redundancy is
designed in.
Alarms are visible by NOC from all sites.