Anchor Data Centre Specifications

Facility Summary

AC power To support all racks 15 Amp single phase to 32 Amp three phase
DC Power Available
UPS120 kVA dual feed with infrastructure in place to total 240 kVA with 100% diversity, 1 hour minimum back up
A/CUnder floor distribution with top return; Multiple water cooled condensers to support full accommodation of the area with 20% extra capacity; Cooling towers servicing Sydney Co-Location 1 & 2
Preaction fire protectionDual, above and under raised floor
Vesda smoke alarmDual, above and under raised floor
Gaseous fire protection (FM200)Dual, above and under raised floor
Generator870 kVA with fuel capacity to last 3 days 24 hour run with no refill
Raised floor500 mm high with under floor cable tray system, air conditioning, dual fire protection and smoke detection system
Cable tray systemUnder floor system
Fibre delivery systemAbove ground - ducted. Top entry required to racks
Lifting platform 1 T to raise equipment to raised floor level
Racks19" by 47 RU, supplied, installed and pre-wired by Anchor, fully enclosed with glass anti-static door, lockable, bottom entry for air, power and data cabling, fibre top entry, top exhaust air
Security Access card with escort. Card Access required for both the floor & room. CCTV on doors & cabinet rows

Service Components

Power

All sites are designed to provide sufficient power supplies to service all equipment within each facility. All power is backed up by specifically designed back up facility such as generator and UPS.

Direct Current (-48V DC)

All facilities are equipped with state of art Direct Current (DC) equipment. The equipment generally consists of rectifier(s), batteries and distribution equipment/boxes. 4-hour batteries are installed at all sites. All batteries are charged from mains (AC) supply. Custom designed, installed and methodically maintained emergency diesel generator automatically backs this up. Loss of power is immediately visible at NOC from all sites. NOC manned 24x7x365 to respond immediately to any loss of power.

Alternate Current (240V AC)

AC power will be supplied as an option to the Co-Location customer. AC will be supplied between 10 to 32 Amp single phase. If the customer will require 3-phase supply this can be accommodated up to 32 Amps 3 phase.

UPS

All AC power is protected by UPS backup.

Generator Back-Up

AC power supply is backed up at all sites by generator and ancillary equipment. All generator systems are supplied with fuel tanks with fuel capacity of minimum 3 days, 24 hours per day at maximum loads. Generators are appropriately maintained and test run on monthly basis. The service and test runs do not require shut-down. Operations and Customer Care will coordinate with customers to ensure they are aware of impending tests. These shutdowns do NOT cause any loss of power to customer equipment.

Floor coverings

All floors are covered by antistatic vinyl.

Grounding

All sites have dual grounding protection: Building earth - all racks, cable trays and non-communication equipment is bonded to it Technical (Communications) earth – all communication equipment is bonded to it via communications earth bars located within the racks.

Fire Protection

Fire protection is provided at Anchor Co-Location sites in the following form: VESDA smoke detection and alarm system Pre-action fire protection FM 200 gaseous system Connection to house fire control system Alarms are visible by NOC from all sites

Air Conditioning

All sites have minimum 20% redundant capacity of cooling. Air conditioning is specifically designed to site-specific conditions to deliver constant environmental climate of 22°C and humidity level of 49%. Air conditioning units are state of art design. Units are either water or air-cooled. Where water coolers are employed minimum of 20% redundancy is designed in. Alarms are visible by NOC from all sites.